C9 (60 Hz)

Producing reliable power from 180 ekW to 300 ekW at 60 Hz, our C9 diesel generator sets are made to meet your standby and prime applications. Each is designed to meet ISO 8528-5 transient response requirements and accept 100 percent rated load in one step. All C9 generator sets are engineered to EPA Stationary Emergency (Tier 3) emissions standards — it’s how we’re helping protect and power the world you live in. Seismic certification is also available to maintain power during unexpected disturbances. Our integrated control system, including ATS and switchgear, ensures a consistent power supply and connection to your fleet through on-site and remote monitoring options. The EMCP 4 control panel, with a user-friendly interface, puts our management and diagnostic tools in one. We offer a wide range of accessories and bolt-on system expansion attachments so you can adapt your generator sets to your needs. Find flexible packaging options to work with your spatial requirements and environmental conditions. Even select from UL 2200 and CSA certified package options for added safety. Tailor your C9 generator sets to take on today’s power needs — and tomorrow’s.

Overview

Producing reliable power from 180 ekW to 300 ekW at 60 Hz, our C9 diesel generator sets are made to meet your standby and prime applications. Each is designed to meet ISO 8528-5 transient response requirements and accept 100 percent rated load in one step. All C9 generator sets are engineered to EPA Stationary Emergency (Tier 3) emissions standards — it’s how we’re helping protect and power the world you live in. Seismic certification is also available to maintain power during unexpected disturbances. Our integrated control system, including ATS and switchgear, ensures a consistent power supply and connection to your fleet through on-site and remote monitoring options. The EMCP 4 control panel, with a user-friendly interface, puts our management and diagnostic tools in one. We offer a wide range of accessories and bolt-on system expansion attachments so you can adapt your generator sets to your needs. Find flexible packaging options to work with your spatial requirements and environmental conditions. Even select from UL 2200 and CSA certified package options for added safety. Tailor your C9 generator sets to take on today’s power needs — and tomorrow’s.

Generator Set Specifications

Minimum Rating180 ekW
Maximum Rating300 ekW
Voltage220-480 Volts
Frequency60 Hz
Speed1800 RPM

Generator Set Configurations

Emissions/Fuel StrategyLow Fuel Consumption, U.S. EPA Certified for Stationary Emergency Use only ( Tier 3 Nonroad Equivalent Emission Standards)

Engine Specifications

Engine ModelC9 ATAAC, I-6, 4-Stroke Water-Cooled Diesel
Bore4.41 in
Displacement537.01 in³
Stroke5.87 in
Compression Ratio16.1:1
AspirationAir to Air Aftercooled
Governor TypeAdem™A4
Fuel SystemHydraulic electronic unit injection

Exhaust System

  • Exhaust manifold; dry

Air Inlet System

  • Aftercooler core
  • Turbocharger

Fuel System

  • Primary fuel filter w/integral water separator and secondary filter
  • Fuel cooler
  • Fuel priming pump
  • Flexible fuel lines
  • Engine fuel transfer pump

Generators and Generator Attachments

  • Brushless, self-excited 2/3 pitch, random wound
  • IP23 protection
  • Insulation class H and temperature rise
  • Power centre, IP22 bottom cable entry
  • Segregated low voltage wiring panel

Governing System

  • Cat electronic governor (ADEM A4)

Lube System

  • Oil cooler
  • Lubricating oil
  • Oil filter and dipstick
  • Oil drain lines with valve; piped to edge of base
  • Fumes disposal; piped to front of radiator

Protection System

  • Safety shutoffs for:
  • High water temperature
  • Overspeed
  • Low oil pressure

Cooling System

  • Coolant drain line with valve; terminated on edge of base
  • Fan and belt guards
  • Coolant level sensor
  • Thermostats and housing, full open temperature 92 deg C (198 deg F)
  • Coolant level sight gauge
  • Jacket water pump, gear driven, centrifugal
  • Caterpillar extended life coolant

Starting / Charging System

  • 24-Volt electric starting motor
  • 24-Volt, 45 amp charging alternator

Control Panels

  • EMCP4.4 control panel

General

  • Paint, Caterpillar Yellow
  • Vibration damper
  • Parts book
  • Operation and maintenance manual pack and OMM storage compartment, wiring diagrams included