C32 (60 Hz)

Producing reliable power from 830 ekW to 1000 ekW at 60 Hz, our C32 ACERT™ diesel generator sets are made to meet your mission critical, continuous, standby and prime applications. We’ve designed each to ISO 8528-5 transient response requirements and to accept 100 percent rated load in one step. Generator sets range from low fuel consumption systems to EPA Stationary Emergency (Tier 2) certification. Seismic certification is also available for select models, ensuring you maintain power after unexpected disturbances. Our integrated control system, including ATS and switchgear, protects your power supply and keeps you connected through on-site and remote monitoring options. We offer easy-to-use EMCP control panel options, combining your management and diagnostic tools in one. The EMCP 4.4 controller provides multi-generator set paralleling capability, giving you the ability to add generator sets to match your growing power requirements. Browse a broad range of accessories and bolt-on system expansion attachments. Find flexible packaging to fit unique spatial requirements and environmental conditions. Even extend the safety of your operation with UL 2200 and CSA certified package options. Our C32 generator sets are made for demands, so you can make yours.

Overview

Producing reliable power from 830 ekW to 1000 ekW at 60 Hz, our C32 ACERT™ diesel generator sets are made to meet your mission critical, continuous, standby and prime applications. We’ve designed each to ISO 8528-5 transient response requirements and to accept 100 percent rated load in one step. Generator sets range from low fuel consumption systems to EPA Stationary Emergency (Tier 2) certification. Seismic certification is also available for select models, ensuring you maintain power after unexpected disturbances. Our integrated control system, including ATS and switchgear, protects your power supply and keeps you connected through on-site and remote monitoring options. We offer easy-to-use EMCP control panel options, combining your management and diagnostic tools in one. The EMCP 4.4 controller provides multi-generator set paralleling capability, giving you the ability to add generator sets to match your growing power requirements. Browse a broad range of accessories and bolt-on system expansion attachments. Find flexible packaging to fit unique spatial requirements and environmental conditions. Even extend the safety of your operation with UL 2200 and CSA certified package options. Our C32 generator sets are made for demands, so you can make yours.

Generator Set Specifications

Minimum Rating830 ekW
Maximum Rating1000 ekW
Voltage220 to 4160
Frequency60 Hz
Speed1800 RPM

Generator Set Configurations

Emissions/Fuel StrategyLow Fuel Consumption, Low Emissions, EPA Certified for Stationary Emergency Application (Emits Equivalent U.S. EPA Tier 2 Nonroad Standards)

Engine Specifications

Engine ModelC32 TA, V-12, 4-Stroke Water-Cooled Diesel
Bore5.71 in
Displacement1958.86 in³
Stroke6.38 in
Compression Ratio15.0:1
AspirationTA
Governor TypeAdem™A4
Fuel SystemMEUI

Air Inlet System

  • Single element canister type with service indicator

Control Panel

  • EMCP 4.2B
  • Control Features
  • Digital Indicators
  • Warning Shutdowns
  • Programmable Protective Relaying Functions
  • Communications

Cooling System

  • ATAAC
  • Radiator fan and fan drive
  • Fan and belt guards
  • Coolant drain line with valve
  • Low coolant level sensor
  • Caterpillar Extended Life Coolant

Exhaust System

  • Exhaust manifold - Dry
  • 203mm (8in) ID round flanged outlet

Fuel System

  • Primary fuel filter with water separator
  • Secondary fuel filter
  • Fuel cooler
  • Fuel priming pump

Generators and Attachments

  • 3 Phase brushless
  • Salient pole
  • Integrated voltage regulator (IVR)
  • 6 Lead
  • Winding temperature detectors
  • Internal excitation
  • NEMA Class H insulation
  • Class H temperature rise at 40C ambient
  • Reactive droop
  • Bus bar connections, top center mounted, top cable entry
  • IEC standard hole pattern
  • Permanent magnet

Governing System

  • ADEM(tm) A4

Lube System

  • Lubricating oil
  • Gear type lube oil pump
  • Integral lube oil cooler
  • Oil filter, filler and dipstick
  • Oil drain lines and valve
  • Fumes disposal

Mounting System

  • Rails - engine/generator/radiator mounting
  • Rubber anti-vibration mounts

Power Termination

  • Bus Bar

Starting and Charging

  • 24-volt electric starting motor
  • 45 amp charging alternator
  • Battery, rack and cables
  • Battery disconnect switch

General

  • Caterpillar Yellow with high gloss black rails & radiator
  • RH Service
  • Flywheel and flywheel housing-SAE
  • SAE Standard Rotation